- Call on : +44 (0)20 8559 8295
- Open Hours : Mon-Fri 08:00 - 17:30
Premier Security Ballistic & Blast Ltd
Hostile vehicle mitigation (HVM) is a core layer of physical security for any UK data centre carrying Critical National Infrastructure status. Premier Security Ballistic & Blast Ltd designs, manufactures and installs PAS 68 and IWA 14-1 rated HVM bollards, sliding security gates, PIPS HVM and crash-rated curtain walling, including the first glass curtain wall system to pass HVM crash testing, protecting the perimeter line, vehicle interfaces and building facade against vehicle-as-a-weapon and vehicle-borne improvised explosive device (VBIED) attack.
A vehicle is the most accessible high-impact weapon available to an attacker. A heavy goods vehicle travelling at speed can carry a significant explosive payload to within metres of a target, or be used directly as a battering ram to breach a perimeter and gain access to high-value compute hardware. For data centres, where a single facility can underpin national banking, government, healthcare and cloud services, the consequence of a successful vehicle attack extends far beyond the site itself.
The September 2024 designation of UK data centres as Critical National Infrastructure has sharpened expectations around perimeter protection. NPSA guidance now expects operators of high-criticality sites to demonstrate a proportionate, layered HVM scheme derived from a Vehicle Dynamics Assessment and a documented Operational Requirement. Increasingly, planning authorities and insurers also expect to see crash-rated mitigation at the perimeter and vehicle approaches of new hyperscale and colocation developments.
HVM in the NPSA layered model: Hostile vehicle mitigation sits in the outermost layers of NPSA's "Deter, Detect, Delay" model. Effective HVM keeps a hostile vehicle at a safe standoff distance, denies vehicle-borne access to the building, and channels legitimate traffic through controlled, rated entry points such as sliding gates and rising bollards.
HVM products are rated by their ability to stop a defined vehicle travelling at a defined speed. Two standards dominate UK and international specification: PAS 68 and IWA 14-1. Premier's HVM products are independently impact-tested and certified to both, so the choice can be driven by operator preference and portfolio consistency rather than product availability.
PAS 68 is the original BSI Publicly Available Specification for vehicle security barriers and remains the most commonly cited HVM standard on UK data centre projects. It defines a standardised impact test and a structured way of expressing the result, covering the vehicle, its mass, the test speed, the impact angle and how far the vehicle and its major debris penetrated beyond the barrier.
IWA 14-1 is the ISO International Workshop Agreement that harmonises vehicle security barrier testing internationally. It is closely aligned with PAS 68 and is increasingly specified where multinational operators or international design teams require a globally recognised rating across their portfolio. Many Premier HVM products carry both PAS 68 and IWA 14-1 classifications.
A PAS 68 classification looks complex but decodes simply. Take the example V/7500[N3]/48/90:5.0:
| Element | Example Value | Meaning |
|---|---|---|
| Test type | V | Vehicle impact test |
| Vehicle mass | 7500 | Test vehicle weighed 7,500 kg |
| Vehicle type | [N3] | Rigid heavy goods vehicle category |
| Test speed | 48 | Impact speed of 48 km/h (around 30 mph) |
| Impact angle | 90 | Vehicle struck the barrier head-on at 90 degrees |
| Penetration | 5.0 | Vehicle penetrated 5.0 metres beyond the barrier line |
The lower the penetration figure, the better the barrier performed. For data centre applications, the specifier selects the vehicle type, mass and speed that reflect the credible threat at each entry point, then chooses a barrier whose tested penetration keeps the building outside the standoff distance.
| Category | Vehicle Type | Typical Test Mass |
|---|---|---|
| M1 | Car | 1,500 kg |
| N1 | Small van / light goods | 2,500 kg |
| N2 | Medium goods vehicle | 3,500 to 7,500 kg |
| N3 | Rigid heavy goods vehicle | 7,500 kg and above |
| Aspect | PAS 68 | IWA 14-1 |
|---|---|---|
| Origin | BSI (UK Publicly Available Specification) | ISO International Workshop Agreement |
| Geographic use | Dominant on UK projects | Used internationally |
| Penetration measurement | Measured from rear of barrier | Measured from front face of barrier (can differ) |
| Recognition | Recognised by NPSA | Recognised by NPSA |
| Typical UK data centre use | Primary specification | Multinational portfolio specification |
Specifier note: PAS 68 and IWA 14-1 measure penetration from different reference points, so a like-for-like rating can read slightly differently between the two standards. Always compare the underlying test vehicle, mass, speed and penetration distance rather than the headline label alone. Premier supplies full test certificates for every HVM product.
An effective HVM scheme is not a catalogue of products, it is a designed response to an assessed threat. Premier works with security consultants and design teams to develop HVM schemes that satisfy NPSA expectations while keeping the site operational and accessible to legitimate traffic.
HVM and the building facade: Where standoff distance is constrained by a tight urban site (common around London-edge and M4 corridor data centres), the building envelope itself can be hardened. Premier's HVM crash-tested glass curtain wall lets architects achieve a rated facade where a conventional standoff perimeter is not achievable, integrating ballistic and blast resistance into the same assembly.
Premier manufactures and installs the full range of HVM products required across a data centre site, from the outer perimeter line through to the building facade. Every product is independently impact-tested and certified to PAS 68 and, where required, IWA 14-1.
| Product | Application | Notes |
|---|---|---|
| HVM bollards | Perimeter line, building approaches, pedestrian zones | Static, removable and automatic rising options; PAS 68 and IWA 14-1 rated; foundation and shallow-mount versions available |
| Sliding security gates | Vehicle entrances, loading bay access | Crash-rated tracked and cantilever sliding gates combining HVM performance with LPS 1175 forced entry resistance |
| PIPS HVM | Perimeter intrusion and vehicle mitigation combined | Integrated perimeter solution merging hostile vehicle mitigation with intrusion protection along the site boundary |
| HVM curtain walling | Building facade where standoff is constrained | The first glass curtain wall to pass HVM crash testing; combined ballistic (FB7), blast (EXV10) and LPS 1175 (E10) ratings available |
| Road blockers & barriers | Controlled high-threat vehicle entry points | Rising road blockers and rated barriers for active control of vehicle access at gatehouses and screening areas |
Premier's PAS 68 and IWA 14-1 rated bollards provide a discreet but highly effective perimeter line for data centres. Static bollards protect fixed lines and building approaches, automatic rising bollards control vehicle entry points, and removable bollards allow occasional access for maintenance and deliveries. Shallow-mount foundation options suit sites with underground services or limited excavation depth.
For vehicle entrances and loading bays, Premier's crash-rated sliding gates combine HVM impact resistance with LPS 1175 forced entry resistance in a single product, controlling vehicle access without creating a weak point in the perimeter line. Tracked and cantilever configurations are available to suit ground conditions and opening widths.
Premier's HVM crash-tested glass curtain wall is the standout product for data centres on constrained sites. As the first glass curtain wall system to pass HVM crash testing, it allows a rated, glazed facade where conventional standoff cannot be achieved, and can be specified with combined ballistic, blast and LPS 1175 ratings to harden the entire building envelope in one assembly.
Includes HVM scheme guidance, PAS 68 and IWA 14-1 rating selection, standoff and Vehicle Dynamics Assessment basics, and how Premier's HVM products integrate with the wider building envelope.
Get the ChecklistHostile vehicle mitigation is the use of crash-rated barriers, bollards, gates and hardened building elements to stop a vehicle being used as a weapon, whether as a direct ram-raid or to deliver a vehicle-borne explosive payload. For data centres, HVM keeps hostile vehicles at a safe standoff distance and denies vehicle-borne access to high-value compute hardware.
Both standards are recognised by NPSA and accepted on UK data centre projects. PAS 68 is the original UK specification and the most commonly cited; IWA 14-1 is the ISO-aligned successor preferred where international operators require a globally recognised rating. Premier's HVM products are tested to both, so the choice can be based on operator and portfolio preference.
The rating is derived from a Vehicle Dynamics Assessment, which models the credible vehicle type, mass and the maximum speed achievable at each approach, combined with the standoff distance the building facade requires. The selected barrier must have a tested penetration distance that keeps the impacting or detonating vehicle outside that standoff line. Premier can support this assessment with security consultants as part of a specification review.
The two standards measure vehicle penetration from different reference points, so an apparently similar rating can read slightly differently. The safest approach is to compare the underlying test data (vehicle category, mass, speed, impact angle and penetration distance) rather than the headline classification alone. Premier provides full test certificates for direct comparison.
Yes. Where site constraints prevent a conventional standoff perimeter, the building envelope itself can be hardened. Premier's HVM crash-tested glass curtain wall, the first glass curtain wall to pass HVM crash testing, provides a rated glazed facade and can be specified with combined ballistic, blast and LPS 1175 forced entry ratings in the same assembly.
Yes. Premier's crash-rated sliding security gates combine PAS 68 or IWA 14-1 HVM performance with LPS 1175 forced entry resistance in a single product, so the vehicle entry point does not become a weak link in the perimeter line. This is a common requirement at data centre loading bays and main vehicle entrances.
Premier's team works with security consultants, architects and main contractors to develop PAS 68 and IWA 14-1 rated HVM schemes derived from your Operational Requirement and Vehicle Dynamics Assessment, integrated with the wider building envelope. Get in touch for a no-obligation specification review.
Request a Specification Review